The main difference between increased safety "e" and non sparking "nA" explosion-proof motors

SINO Testing Services

| 2020-08-12|Return

The increased safety type "e" motor and the spark free type "nA" motor are very similar in general structure, and even in terms of test items and inspection requirements, they are quite similar. Many people cannot accurately distinguish the requirements of these two explosion-proof types of motors. Here is a simple comparison in order to stimulate further exploration of these two typesexplosion-proofThe difference between motors.


Explosion proof type definition

“e”Increased safety typeTake additional measures for electrical equipment to improve safety and prevent the possibility of dangerous temperatures, arcs, and sparks under normal operation or specified abnormal conditions.

NA spark free device: a device that structurally minimizes the risk of generating arcs or sparks that can cause ignition under normal usage conditions.

From this perspective, it can be simply said that increased safety motors can prevent arcing and sparks during operation, while the "nA" type, although called spark free, cannot completely prevent and eliminate sparks, but only minimize them to the greatest extent possible. The "nA" device can make the probability of sparks very low, so low that the risk of ignition can reach an acceptable level for people. It is not difficult to understand why the standard stipulates that some increased safety motors (under specific conditions) can reach Gb level, while non sparking motors can only be Gc level.


Comparison of structural and performance requirements

1. Increased safety motors (using current protection devices to prevent exceeding the limit temperature) have requirements for the starting current ratio IA/IN and tE time, which need to be indicated on the motor nameplate. The purpose is to facilitate the selection and configuration of suitable protection devices when using the motor, while spark free motors do not require them.

Both increased safety and non sparking motors have requirements for electrical clearance and creepage distance, but at the same voltage level, the minimum electrical clearance and creepage distance between live parts of increased safety motors are required to be larger than those of non sparking motors (see Table 1 for details), and the material grade of insulation parts used in non sparking motors can be as low as Grade IIIb, while increased safety motors require Grade IIIa or above.

 

Table 1 Different requirements for creepage distance and electrical clearance between increased safety type and non sparking type when voltage level ≤ 250V

3. For the requirements of squirrel cage rotors, increased safety motors need to be evaluated according to Table 4 of GB3836.3-2010 "Potential Air Gap Spark Hazard Assessment for Squirrel Cage Rotor Ignition Hazard Factors", while for non sparking motors, only motors with rated output greater than 100kW and excluding S1 or S2 working conditions need to be evaluated according to Table 6 of GB3836.8-2014 "Potential Air Gap Spark Hazard Assessment for Squirrel Cage Rotor Ignition Hazard Factors" (see Figure 1 for differences), and then decide whether additional measures need to be taken to ensure that the motor does not ignite during start-up and operation.

 

Figure 1 Range of motors requiring air gap spark hazard assessment for increased safety and non sparking types

4. For the requirements of the stator winding insulation system, increased safety motors with a rated voltage exceeding 1kV should have special protective measures to ensure that the casing does not contain explosive gases during start-up, while spark free motors do not have this requirement. It is only recommended to minimize the partial discharge of the high-voltage winding. For windings with a rated voltage ≥ 6.6 kV, it is recommended to use materials that can suppress partial discharge.


Comparison of experimental requirements

All increased safety motors (rated voltage exceeding 1kV) and non sparking motors (Class IIA with loose wound stator rated voltage greater than 1kV or mode wound stator rated voltage greater than 6.6kV, and Class IIB and IIC with rated voltage greater than 1kV) shall undergo steady-state ignition tests of the stator winding insulation system. However, increased safety motors with rated voltage exceeding 1kV shall also undergo transient ignition tests of 10 voltage pulses three times the peak relative ground voltage in a specified explosive gas mixture. Increased safety motors require insulation dielectric strength testing, while spark free motors do not have specific regulations for insulation dielectric strength testing. 

Related Recommendations
Contact us
0755-2102 2109
Add: 13F, Building C, Kangjia Guangming Technology Center, No. 288 Xingxin Road, Guangming District, Shenzhen
Follow us
Copyright: Shenzhen Zhongnuo Testing Technology Co., Ltd. 粵ICP備18004888號
Service Hotline
18924609560
點擊這里給我發消息 1354407946
點擊這里給我發消息 1354407946
主站蜘蛛池模板: 欧美日韩在线播放一区 | 91网站免费观看 | 在线免费视频a | 做爰裸体激情2 | 中文在线观看免费视频 | 国产午夜精品久久久久 | 国产精品视频中文字幕 | 激情久久一区二区 | 美女黄网站免费观看 | 午夜视频中文字幕 | 黄色美女网站免费看 | 成人 精品 | 亚洲成人精品久久 | chinese hd xxxx tube| 欧美18一12sex性处hd | 成人偷拍片视频在线观看 | 国产手机国产手机在线 | 视频一区二区三区在线 | 破处av在线 | 自拍偷拍999 | 中国大陆高清aⅴ毛片 | 欧美黄色小视频 | 精品伊人 | 久久精品一区视频 | 精品三区视频 | 久草视频福利在线观看 | 国产精品视频一区二区三区四 | 日韩a毛片免费观看 | 日韩精品dvd| 91 在线免费观看 | 草草久久久 | 91精品久久香蕉国产线看观看 | 欧美激情性色生活片在线观看 | 北原夏美av | av在线观 | 国产视频在线观看一区二区三区 | 久久久久久久久久亚洲精品 | 一级大黄毛片 | 一级黄色淫片 | 一级黄色影片在线观看 | 精品av在线播放 |